The rated current of the Dada DAM3-250 molded case circuit breaker can reach up to 250A. These electrical devices are suitable for power distribution circuits with an alternating current of 50-60Hz and a rated operating current to 1000A. They can also be used in electric motors for infrequent starting and overload protection as well as protection against short circuiting and undervoltage conditions.
Compared to the DAM1 series, the DAM3 series are designed for smaller volume, higher breaking capacity, offering better energy savings.

Electrical Parameters of DAM3-250 Molded Case Circuit Breaker

Rated current of frame size Inm [A]  

250

Rated current [A]

100-250

100-225

Number of poles

2 / 3 / 4

Rated operating voltage

(AC)50-60HZ [V]

400/690

DC [V]

250/1000

Rated impulse withstand voltage Uimp [KV]

8

Rated insulation voltage Ui [V]

750

Test voltage at industrial frequency for 1 min [V]

3000

Rated ultimate short-circuit breaking capacity Icu [KA]

B

C

N

S

(AC)50-60HZ 220/230V [KA]

30

36

50

75

(AC)50-60HZ 400/415V [KA]

18

25

36

50

(AC)50-60HZ 690V [KA]

6

8

12

15

(DC)250V-2 Poles in series

18

22

30

40

(DC)500V-2 Poles in series

9

12

15

20

(DC)750V-4 Poles in series

16

18

22

30

(DC)1000V-4 Poles in series

13

15

18

25

Rated service short-circuit breaking capacity, Ics [KA]        
(AC)50-60HZ 220/230V [%Icu]

60%

60%

60%

50%

(AC)50-60HZ 400/415V [%Icu]

60%

60%

60%

50%

(AC)50-60HZ 690V [%Icu]

60%

60%

60%

50%

category of utilization (EN 60947-2)

A

Isolation condition

Bitmap

Reference standard

IEC/EN 60947-2/GB 14048.2

Interchangeability

Bitmap

Versions Fixed

Bitmap

Plug-in

Bitmap

Draw-out -

Physical Parameters DAM3-250  Molded Case Circuit Breaker

Endurance

Total cycles

10000

Electrical endurance

1500

Mechanical endurance

8500

 

 

 

 

Basic dimensions-fixed version

 

3/4 Poies W[mm]

70(2P) /104 /139

3/4 Poies H[mm]

59

62.5

H1[mm]

78.5

82

3/4 Poies L[mm]

139

Introduction

The DAM3-250 molded case circuit breaker automatically cuts off the current when the current exceeds the release setting. The molded case refers to the plastic insulator used as the frame of the device to insulate the conductor and the metal grounding component.