2018 High quality 4 Pole Earth Leakage Circuit Breaker – DAM1L-630 CBR ELCB Earth Leakage Protection Circuit Breaker – DaDa Detail:
Introduction
DAM1L series residual current (leakage) circuit breaker (hereinafter referred to as circuit breaker) is a new series of residual current (leakage) successfully developed by using international standard design and advanced manufacturing technology.
Protected moulded case type circuit breaker.
The rated insulation voltage of circuit breakers of this series is 400V (Inm is less than 160A) and 690V (Inm is more than 250A), which is mainly used for ac 50Hz and rated In a power distribution network with a current of 10A~500A and a rated working voltage of 380V/400V, it is used to distribute electric energy and protect the overload and short circuit of lines and power equipment.
Under normal conditions,It can also be used for infrequent switching of lines.
This circuit breaker also has the following protection:
• It provides protection for fire hazards caused by grounding fault current that cannot be detected due to overcurrent protection.
• Provide protection against the danger of increasing ground voltage due to insulation damage;
• Circuit breakers with rated residual action current not exceeding 30mA can be used for personal contact protection.
• Circuit breakers with rated current of 500A and below can also be used for infrequent start, break off during operation and overload and short circuit protection of squirrel cage motors.
DAM1L series circuit breakers can be equipped with electric accessories and mechanical accessories for various purposes, such as separately excited tripping device, auxiliary contact, alarm contact and rotating handle operating mechanism.
This series of circuit breakers are widely used in construction, transportation, tunnel, residence, etc.The delay type in this series of circuit breakers is used for branch lines
Distribution of roads;Adjustable type is used to adjust the residual action current or disconnection time on site.
Advantages
• Range:10A to 500A(AC)
• integral structure, small volume, high breaking capacity, safe and reliable.
• Adjustable magnetic setting(0.8-1times)In.
• Push to trip button provision.
• Separate main and arcing contacts
• Can be adjusted the residual action current or disconnection time according to the actual use.
• Strong anti-interference ability.
• Wide range of accessories.
The working power of the residual current protection circuit of this series of circuit breakers is supplied by the multi-phase power supply (the working power of the protection circuit of early products is supplied by the single-phase power supply)the residual current protection circuit of the device can still operate normally.When the operating power voltage of the circuit breaker’s residual current protection circuit is reduced to 50V, the circuit breaker’s residual current protection circuit can still work normally.(I coherence n=30mA)
This series of circuit breakers are classified into B type (i.e., basic breaking capacity) (Inm less than 100), S type (i.e., standard breaking capacity) and H type (i.e High score breaking capacity (Inm > 160) can be used in different situations.
The main circuit of a circuit breaker is connected in many ways:
Piston front connection
Terminal extension plate front connection
The screw connection at the rear of the piston plate
Earth-Leakage Circuit Breakers
Residual current circuit breaker basic parameters |
|||
COSφ |
Rated current of remnant motion I△n (mA)
|
Rated current of remnant no-motion I△no (mA)
|
Max-Breaking time (S) |
0.2 |
100,300,500 |
50,150,250 |
0.05,0.5, 0.8 |
Rated residual operating current(mA) |
Rated no tripping current value.I△no(mA) |
Residual current value range.(mA)0.5x(I△n+I△no)±0.2I△n |
30 |
15mA |
18mA-27mA |
100 |
50mA |
60mA-90mA |
300 |
150mA |
180mA-270mA |
500 |
250mA |
300mA-450mA |
1000 |
500mA |
600mA-900mA |
Earth-Leakage Circuit Breakers(ELCB) |
|
|||||||
Model |
DAM1-125L |
DAM1-160L |
||||||
Breaking Capacity Code |
B |
N |
S |
B |
N |
S |
||
Rated Current of Frame size- Inm (A) |
125A |
160A |
||||||
Rated Current-In(40,50 or 55℃) (A) |
10 – 12,5 – 16 – 20 – 25 – 32(30) – 40 – 50 – 63(60) – 80 – 100 – 125A |
10- 12,5-16-20 – 25 – 32 – 40 - 50 – 63 – 80 – 100 -125 – 160(150)A |
||||||
Ui (V) |
690V |
690V |
||||||
Ue (V) |
400V |
400/415V |
||||||
Number of Pole |
4P |
4P |
||||||
Icu (KA) |
25 |
35 |
50 |
25 |
35 |
50 |
||
Ics(KA) |
12.5 |
17.5 |
37.5 |
12.5 |
26.25 |
37.5 |
||
Icm(peak)/cos ф (KA) |
40/0.3 |
73.5/0.25 |
105/0.25 |
41/0.3 |
73.5/0.25 |
110/0.25 |
||
(I△m)KA/cosф |
9/0.5 |
19/0.5 |
||||||
Residual current threshold(mA) |
100-300-500 |
100-300-500 |
||||||
Time delay(ms) |
50-500-800 |
50-500-800 |
||||||
Uimp (V) |
10000 |
8000 |
||||||
Dielectric Propery (V) |
2500 |
3000 |
||||||
lonization distance (mm) |
≤30/0 |
≤30/0 |
||||||
Endurance |
Total Cycles |
8000 |
8000 |
|||||
Electrical Life |
1000 |
1000 |
||||||
Mechanical Life |
7000 |
7000 |
||||||
Category (EN 60947-2/IEC 60947-2) |
Main circuit |
A/0 |
A/0 |
|||||
Auxiliary circuit |
AC-15 |
AC-15 |
||||||
Under Voltage Release |
√ |
√ |
||||||
Shunt Release |
√ |
√ |
||||||
Auxiliary Contact |
√ |
√ |
||||||
Alarm Contact |
√ |
√ |
||||||
Auxiliary Contact and Alarm Contact |
√ |
√ |
||||||
Handle Operation Mechanism |
√ |
√ |
||||||
Electrical Operastion Mechanism |
√ |
√ |
||||||
Terminal cover |
√ |
√ |
||||||
Phase seperator |
√ |
√ |
||||||
W (mm) |
3P |
- |
- |
|||||
4P |
101 |
120 |
||||||
L (mm) |
3P |
- |
- |
|||||
4P |
155 |
120 |
||||||
H (mm) |
3P |
- |
- |
|||||
4P |
70 |
70 |
||||||
Weight |
Fixed version 3P/4P |
- |
- |
|||||
Plug-in version 3P/4P |
- |
- |
||||||
Draw out version 3P/4P |
- |
- |
Earth-Leakage Circuit Breakers(ELCB) |
|
|
||||||||
Model |
DAM1-250L |
DAM1-400L |
||||||||
Breaking Capacity Code |
N |
S |
H |
G |
N |
S |
H |
G |
||
Rated Current of Frame size- Inm (A) |
250A |
400A |
||||||||
Rated Current-In(40,50 or 55℃) (A) |
63 – 80-100-125 – 160(180) - 200(225) – 250(320)A |
250 – 315 (350)- 400 – 500A |
||||||||
Ui (V) |
690V |
690V |
||||||||
Ue (V) |
400/415V |
400/415V |
||||||||
Number of Pole |
4P |
4P |
||||||||
Icu (KA) |
35 |
50 |
65 |
85 |
35 |
50 |
70 |
85 |
||
Ics(KA) |
26.25 |
37.5 |
48.75 |
51 |
26.25 |
37.5 |
52.5 |
52.5 |
||
Icm(peak)/cos ф (KA) |
77/0.25 |
114/0.25 |
143/0.2 |
178/0.2 |
70/0.25 |
110/0.25 |
154/0.2 |
187/0.2 |
||
(I△m)KA/cosф |
12/0.3 |
19/0.5 |
||||||||
Residual current threshold(mA) |
100-300-500 |
100-300-500 |
||||||||
Time delay(ms) |
50-500-800 |
50-500-800 |
||||||||
Uimp (V) |
8000 |
8000 |
||||||||
Dielectric Propery (V) |
3000 |
3000 |
||||||||
lonization distance (mm) | ≤30/0※ | ≤60/0※ | ||||||||
Endurance |
Total Cycles |
8000 |
5000 |
|||||||
Electrical Life |
1000 |
1000 |
||||||||
Mechanical Life |
7000 |
4000 |
||||||||
Category (EN 60947-2/IEC 60947-2) |
Main circuit |
A/B |
A/B |
|||||||
Auxiliary circuit |
AC-15 |
AC-15 |
||||||||
Under Voltage Release |
√ |
√ |
||||||||
Shunt Release |
√ |
√ |
||||||||
Auxiliary Contact |
√ |
√ |
||||||||
Alarm Contact |
√ |
√ |
||||||||
Auxiliary Contact and Alarm Contact |
√ |
√ |
||||||||
Handle Operation Mechanism |
√ |
√ |
||||||||
Electrical Operation Mechanism |
√ |
√ |
||||||||
Terminal cover |
√ |
√ |
||||||||
Phase seperator |
√ |
√ |
||||||||
W (mm) |
3P |
- |
- |
|||||||
4P |
140 |
184 |
||||||||
L (mm) |
3P |
- |
- |
|||||||
4P |
210 |
254 |
||||||||
H (mm) |
3P |
- |
- |
|||||||
4P |
103.5 |
103.5 |
||||||||
Weight |
Fixed version 3P/4P |
- |
41.5/5.5 |
5.1/7.1 |
||||||
Plug-in version 3P/4P |
- |
4.6/6 |
6.5/8.5 |
|||||||
Draw out version 3P/4P |
- |
5/6.4 |
6.5/8.7 |
• Icu:O-t-CO test(O:Open maneuver,CO:Close-Open maneuver,t:Waiting duration)
• Ics:O-t-CO-t-CO test(O:open maneuver,CO:Close-Open maneuver,t:Waiting duration)
Product detail pictures:
Related Product Guide:
Our personnel are generally within the spirit of "continuous improvement and excellence", and using the excellent top quality goods, favorable rate and superior after-sales expert services, we try to win every customer's believe in for 2018 High quality 4 Pole Earth Leakage Circuit Breaker – DAM1L-630 CBR ELCB Earth Leakage Protection Circuit Breaker – DaDa , The product will supply to all over the world, such as: Ukraine, Luxembourg, Myanmar, Our company follows laws and international practice. We promise to be responsible for friends, customers and all partners. We would like to establish a long-term relationship and friendship with every customer from all over the world on the basis of mutual benefits. We warmly welcome all old and new customers to visit our company to negotiate business.